Call our sales team +91 88792 19180

Maintenance 2 min read

Fire Alarm Maintenance Checklist: Weekly, Monthly and Half-Yearly

A fire alarm only protects you if it works on the day. Use this simple weekly, monthly and half-yearly routine to keep yours ready.

Ajinkya Fires TeamFire alarm & PA specialists, Mumbai

Every week (5 minutes)

  1. Check the panel shows normal, with no fault or disabled lights.
  2. Test one manual call point with its test key, using a different one each week.
  3. Confirm the sounders can be heard, then reset the panel.
  4. Write the date, the call point tested and any issues in the logbook.

Test at the same time each week so people in the building know it is a test, not a fire.

Every month

  • Look over the standby batteries for swelling or leaks, and check the panel shows mains power.
  • Walk the site and make sure no detector has been covered, painted or blocked by new partitions, racks or false ceilings.
  • Check that call points are visible and not hidden behind furniture or stock.

Every six months (by a technician)

A competent technician should service the whole system twice a year. A typical visit covers:

  • A functional test of every detector with test smoke or heat
  • A battery load test and charger check
  • Sounder and flasher checks in every zone
  • Cable, earth-fault and event-log checks
  • Cleaning or replacing contaminated detectors

Long-term replacement

Smoke detectors slowly lose sensitivity as dust builds up inside them, and most manufacturers recommend replacing them after about 10 years. Standby batteries wear out every few years, so check the date written on them at every service.

Key takeaways

  • Weekly: one call point test, logged.
  • Monthly: a walk-round to spot blocked or covered devices.
  • Every six months: a full service by a technician.

Was this article helpful?

Keep reading

All articles